Steam Shower Installation Requirements: Enclosure, Generator, Electrical and Plumbing

Steam shower under construction with waterproofed backer board walls and a sloped ceiling

Steam shower installation

Steam shower installation requirements come from the installation manual for your generator and from national and local codes. This guide sets ThermaSol's PRO Series III manual beside Mr. Steam's 2025 manuals for its MS, MS Super and MAX generators, noting the MAX rules where they differ. It is a planning guide, not instructions on how to install a steam shower: both manufacturers call for a licensed electrician and a licensed plumber, working to national and local codes.

Quick answer: before the walls close, plan walls, ceiling and floor suitable for steam, with a sloped ceiling; an accessible generator space that is never inside the steam room, outdoors or anywhere water could freeze; a 208 to 240 V circuit sized for the model; a cold water line with a shut-off valve; a drain; and a steam line with no valves. ThermaSol allows the generator up to 50 feet from the shower, and Mr. Steam's sizing allows up to 60 feet of insulated steam piping.

The enclosure

The steam shower requirements start with the room. ThermaSol's manual says to make sure the "walls, ceiling and floor materials are suitable for use with steam." Mr. Steam's manuals say the steam room must be completely enclosed, with full walls, door, floor and ceiling, and recommend a gasketed door for steam containment.

Surfaces. ThermaSol recommends non-porous, moisture-resistant materials such as porcelain or ceramic tile, tempered glass and sealed grout, and says natural stone is an option but must be sealed regularly. Mr. Steam calls for water-resistant, non-corrosive, non-porous surfaces such as tile, marble or molded acrylic; its MAX manual adds that they must be heat-resistant.
Acrylic and fiberglass. ThermaSol says acrylic walls must be steam rated by their manufacturer and that it "only recommends specific generators for acrylic modules," so confirm the model before you order. Mr. Steam says to consult the enclosure maker and to use its Acrylic Shield at the steam head.
Floor. Mr. Steam's manuals call for nonslip flooring or floor strips and a floor drain. ThermaSol says to check the safe use of your flooring in a steam application with your contractor or flooring manufacturer.
Windows and air devices. Mr. Steam says steam room windows should be double-paned, tempered safety glass, and that no heating, venting or air conditioning devices should be installed inside the steam room.

Still deciding on steam? See our infrared sauna vs steam room comparison.

Ceiling height and slope

ThermaSol's manual calls for a ceiling slope of 1 inch per foot, and its FAQ explains that a sloped ceiling helps keep condensation from dripping during a session. Mr. Steam's MS and MS Super manual says the ceiling should be sloped so condensate does not drip, but gives no amount, and the MAX manual does not mention slope. Agree on the steam shower ceiling slope with your contractor before framing.

On height, ThermaSol does not recommend a ceiling over 10 feet, says lowering it to 8 feet "helps create a more efficient steam room," and sizes up one unit for every foot above 8 feet. Mr. Steam's manuals say to limit the ceiling to 8 feet and add 15 percent to the volume for each foot above 8 feet, to a maximum of 10 feet.

Example: a 4 × 5 ft tiled shower with a 9 ft ceiling holds 180 cubic feet. ThermaSol's rules call for the PROIII-395 (the PROIII-240, plus one size for the 9 ft ceiling); Mr. Steam's call for the MS400R (180 + 15% = 207 cubic feet). Run your numbers in our size calculator; our steam shower generator guide covers both brands' sizing rules.

Where the generator goes

Both manuals say to place the generator as near as practical to the steam room, and both rule out the same places for a steam generator installation: inside the steam room, outdoors, and an unheated attic or anywhere water could freeze; that last rule covers the plumbing lines too. Typical locations are a closet, vanity cabinet, climate-controlled attic or basement for ThermaSol; a closet, vanity cabinet, heated attic or basement for Mr. Steam's MS and MS Super; and a heated attic or basement for MAX.

Rule ThermaSol PRO Series III Mr. Steam MS and MS Super Mr. Steam MAX
The space Dry, non-combustible, well ventilated, finished and climate-controlled Ambient up to 113°F (45°C); away from flammable or corrosive chemicals and high chlorine Same, in a room with ventilation; never in a vanity, other small enclosed space or under the bench
Mounting Upright and level, connections on top Upright on a solid, level surface; wall mounting allowed, with supports Upright on a solid, level surface; never hung on a wall
Clearance 6 in on all sides 12 in at both ends and on top; zero to combustibles 18 in on the left, 21 in on top; zero to combustibles
Distance Up to 50 ft from the shower Up to 60 ft of insulated steam piping; beyond that, consult the factory Same as MS and MS Super

ThermaSol says the generator "must remain accessible at all times," never behind walls or inside a bench, and recommends PowerFlush maintenance every 1,000 minutes of use; Mr. Steam's manuals call for opening the manual drain valve every 2 months, or more often in hard water areas. If your room calls for a MAX such as the MX4R, plan a room with ventilation for it.

Planning the generator space?

Send us your shower's dimensions, wall material and ceiling height, and we will reply with the model each brand's rules call for and a quote.

Get Pricing

Electrical requirements

Steam shower electrical requirements depend on the model's current draw, so choose the generator before the circuit is planned.

Electrician installing a dedicated two-pole breaker in a home electrical panel for a steam generator

ThermaSol PRO Series III

ThermaSol requires a 208 to 240 V single-phase supply, with each generator on its own separate breaker, copper wire only with a minimum temperature rating of 90°C (type THHN), and a licensed electrician for all electrical work. Its manual lists the current draw and connection for each model:

Model Power Amps Connection
PROIII-84 6 kW 28 A NEMA 6-30P
PROIII-140 8 kW 37 A NEMA 6-50P
PROIII-240 10 kW 46 A NEMA 6-50P
PROIII-395 11 kW 55 A Hardwire
PROIII-575 15 kW 69 A Hardwire
PROIII-750 20 kW 92 A Hardwire
PROIII-1200 24 kW 110 A Hardwire

A ThermaTouch2 control also comes with a Power Distribution Module (PDM) that requires 110 VAC power.

Mr. Steam MS, MS Super and MAX

Mr. Steam's MS and MS Super manual says to use a 240 V unit when the supply is greater than 208 V and a 208 V unit for 208 V power, noting that most homes have 240 V single-phase service; 208 V and three-phase generators are available on request. The manuals also call for:

Overcurrent protection. A separate circuit breaker for MS and MS Super; fuses or a circuit breaker for MAX.
A disconnect. Within sight of the generator, or lockable in the open position.
Conductors. Minimum 90°C/300 V rated insulated copper, sized to national and local code for the current in Mr. Steam's chart; NM cable, where codes allow it, may need a larger size.
Model Series Power Amps at 240 V, single phase
MS90R MS 5 kW 21 A
MS150R MS 6 kW 25 A
MS225R MS 7.5 kW 32 A
MS400R MS 9 kW 38 A
MSSUPER1R MS Super 10 kW 42 A
MSSUPER2R MS Super 12 kW 50 A
MSSUPER3R MS Super 15 kW 63 A
MX4R MAX 20 kW 84 A
MX5R MAX 24 kW 100 A
MX6R MAX 30 kW 125 A

Amps are from Mr. Steam's manuals; have a licensed electrician size the wire from the chart and your local code. Our ThermaSol buying guide and Mr. Steam buying guide cover each line's models.

Water supply

The steam shower plumbing covers the cold water supply, the drain connections and the steam line. Both brands connect the generator to the cold water line through a 3/8 inch connection with a shut-off valve; the pipe materials differ.

ThermaSol. Tee into the cold water line and run a 3/8 inch NPT line to the supplied braided hose, with an accessible brass shut-off valve and recommended unions on rigid lines. Use copper or brass fittings only, with no galvanized fittings and no PEX or PVC tubing. ThermaSol recommends an in-line water filter and says to flush the line into a pail before connecting.
Mr. Steam. Brass piping or rigid copper tubing with unions; the water feed line may be flexible copper tubing, braided hose, PVC or PEX if local codes permit. A strainer and a feed pressure of 15 to 20 psi (to reduce operating noise) are recommended, and an anti-water hammer device and a backflow preventer go in as required. Flush the water supply and steam piping before connecting.

Mr. Steam also says to test the water before installation; its recommended feedwater limits include hardness of 8 to 85 ppm and a pH of 8.0 to 11.4.

Drain, drain pan and safety valve

ThermaSol's PRO Series III page lists a stainless steel drain pan as included, and its manual says the pan "must be installed on all generator installations," with its 3/4 inch drain plumbed to an approved drain. The manual also says not to plumb the pressure relief valve into the steam line.

Mr. Steam sells drip pans separately but "strongly recommends the use of a drip pan in the unlikely event of a plumbing leak." The pan has a 3/4 inch fitting and drains by gravity. Mr. Steam's other drain rules:

Drain valve. 1/2 inch NPT on MS and MS Super, 1 inch on MAX, draining by gravity to a drain line that meets national and local codes. The MS and MS Super drain should not share an under-sink trap unless the generator is mounted higher than the sink; a MAX drain never connects to one.
Not into the enclosure. Never drain into the steam enclosure or anywhere people could touch the drain water: in a power failure, the AutoFlush valve opens and may discharge boiling water.
Safety valve. Pipe its outlet where local codes permit. Never fit a shut-off valve or plug at the outlet, and never join it to the drain line or the steam piping; the drain valve must not connect to the steam piping either.
AutoFlush. Mr. Steam's optional AutoFlush drains the generator about 2 hours after each use and needs a drain line lower than the AutoFlush assembly.

The steam line

Both manuals guard against condensate collecting at a low point and blocking the steam; Mr. Steam warns that this may discharge boiling water through the steam head, a scalding hazard.

Insulated copper steam line run through open wall framing toward a steam shower, one of the steam shower installation requirements

ThermaSol PRO Series III

Pipe. 1/2 inch brass pipe or copper tubing to the steam head rough-in fitting, as codes permit; 3/4 inch for the PROIII-750 and PROIII-1200.
Route. No valves and no traps. The line may run up and then down once, or horizontally, but never down and then up.
Pitch. Back toward the generator before any up or down turn and toward the steam room after it; avoid exactly level runs.
Insulation. Steam-rated insulation if the run exceeds 10 feet or is exposed to cold areas.

Mr. Steam

Pipe. 3/4 inch brass pipe or copper tubing, as codes permit, with no valves. For MAX, never less than 3/4 inch from the generator to the tee, routed so each steam head gets an equal amount of steam.
Pitch. 1/4 inch per foot toward the steam head or the generator. The MAX manual adds that running the piping down and then up creates a steam trap.
Insulation. Fiberglass pipe insulation or similar, rated 212°F or higher.
Fittings. 45-degree elbows are preferred over 90-degree elbows to reduce noise. Mr. Steam's optional AromaSteam system needs a 90-degree tee on the steam piping, so plan it before the walls close.

Steam head placement

In new construction, the steam head rough-in fitting goes in before the wall is finished; ThermaSol's manual reminds installers not to forget it.

Brass steam head rough-in fitting protruding from a freshly tiled shower wall near the floor

ThermaSol

Height and corners. 24 inches from the floor or bathtub rim (the No-Touch steam head goes 12 inches above the shower floor), and at least 6 inches from any corner.
Away from people and the control. Not near or beneath seating, and as far as possible from the bathing position and from the in-shower controller.
Sealed and facing up. The housing is sealed to the wall so vapor cannot get behind it (a housing kit comes with the PRO Series III), and the steam head faces up so its aroma well can dispense steam.

Mr. Steam

Height. 6 to 12 inches above the floor, or 6 inches above the top edge of a tub.
Clearances. Not within 12 inches of a wall (to reduce noise), not where direct steam would hit the door seals, and where a bather cannot touch the steam head or the direct steam.
Mounting. Flush with the wall, oil well facing up, with the gap around the pipe sealed with silicone. Use Mr. Steam's Acrylic Shield on acrylic or other non-heat-resistant enclosures.
MAX. Two or more steam heads, spaced evenly; the manual says never to use fewer than two.

Control placement and cable

ThermaSol

Placement. ThermaTouch2, SignaTouch and MicroTouch controls "must be installed inside the shower and mounted 60 inches from the floor to the center of the controller," as far as possible from the steam head and as close as practical to where the user sits.
Openings. The ThermaTouch2 needs a cutout 3.5 inches deep (7.5 × 5.5 inches for the 7-inch, 10 × 6.625 inches for the 10- and 15-inch), with at least 3.5 inches clear around the mud ring cutout.
Cable. The supplied 50-foot cable, preferably in electrical conduit, never pinched, nailed or stapled, and never wrapped around the steam line or routed where the hot line could melt it.

Mr. Steam

Placement. Inside or outside the steam room. Outside, Mr. Steam's manuals call for a remote temperature probe (part number MSTS) to be installed inside the steam room. Inside, 4 to 5 feet above the floor near the seating area, on a vertical wall, never above or near the steam head.
Cable. 30 feet standard and 60 feet maximum, in a dedicated 1 inch conduit, never shared with power lines or run close to hot water or steam piping.

Our steam shower control guide compares the controls. Choose yours in the configurator on each generator's product page before rough-in. Mr. Steam add-ons that wire back to the generator mean opening the wall if you add them later.

Pre-construction checklist

Review this with your contractor before framing; MAX differences are in brackets. For a full brand comparison, see ThermaSol vs Mr. Steam.

Item ThermaSol PRO Series III Mr. Steam [MAX]
Enclosure Walls, ceiling and floor suitable for steam; non-porous, moisture-resistant surfaces Fully enclosed; gasketed door recommended; non-porous, water-resistant surfaces [also heat-resistant]; nonslip floor; floor drain
Ceiling Slope 1 in per foot; not over 10 ft (recommended) Sloped [no statement]; limit to 8 ft; sizing stops at 10 ft
Generator space Dry, ventilated, climate-controlled, always accessible; 6 in on all sides; up to 50 ft away Level surface; ambient up to 113°F; 12 in at ends and top [18 in left, 21 in top; ventilated room; no vanity or wall mounting]; up to 60 ft of insulated piping
Power 208 to 240 V, single phase, own breaker; 28 to 110 A 240 V single phase standard; separate breaker [fuses or breaker]; 21 to 63 A at 240 V [84 to 125 A]
Water Cold line, 3/8 in NPT, shut-off; copper or brass fittings only; no PEX or PVC Cold line, 3/8 in NPT, shut-off; brass or rigid copper; 15 to 20 psi recommended
Drain Included drain pan required; 3/4 in drain Drain valve 1/2 in [1 in]; drip pan strongly recommended
Steam line 1/2 in (3/4 in for PROIII-750 and PROIII-1200); no valves or traps 3/4 in; no valves; pitch 1/4 in per foot; insulation rated 212°F or higher
Steam head 24 in up (No-Touch 12 in); 6 in from corners 6 to 12 in up; at least 12 in from walls [two or more]
Control Inside the shower, 60 in to center; 50 ft cable Inside at 4 to 5 ft, or outside with a remote temperature probe in the room; 30 ft cable, 60 ft maximum

Warranty and installation

ThermaSol's manual says products must be installed in accordance with the installation instructions provided, and that failure to do so may invalidate the warranty at the manufacturer's discretion. Its exclusions include installation that fails to observe national or local plumbing or electrical codes, installation that does not permit proper access for service, service by unauthorized personnel, and use of a residential unit in a non-residential or commercial application, including a hotel. After the 2-year in-home warranty, ThermaSol's lifetime factory limited warranty replaces defective parts and covers labor at the factory, with removal, installation and shipping left to the customer, so access matters for the life of the generator. ThermaSol requires proof of purchase from an authorized reseller to start any warranty process.

Both Mr. Steam manuals say their generators are for residential use only, that commercial or other non-residential use voids the warranty, and that altering or modifying any Mr. Steam product voids it too. The MS and MS Super manual adds that malfunction due to power spikes, lightning, fire, freezing or flooding is not covered. Sauna Republic is an authorized dealer of both brands.

Commercial project? ThermaSol provides no warranty for residential generators used in hotels, spas, gyms or short-term rentals. See our guide to commercial steam rooms by facility type.

Frequently asked questions

Can I install a steam shower generator myself?

Both manuals call for licensed trades: ThermaSol requires a licensed electrician and a qualified licensed plumber, and Mr. Steam says all installation and service are to be performed only by qualified and licensed electricians and plumbers.

How much slope does a steam shower ceiling need?

ThermaSol's manual calls for 1 inch per foot. Mr. Steam's MS and MS Super manual says the ceiling should be sloped but gives no amount, and the MAX manual does not address slope.

Can the generator go in a vanity cabinet?

For ThermaSol and Mr. Steam's MS and MS Super, a vanity cabinet is one of the typical locations their manuals list, as long as it meets each brand's other location rules, including 6 inches of clearance on all sides for ThermaSol and 12 inches at both ends and on top for MS and MS Super. For MS and MS Super, the generator drain should not share an under-sink trap unless the generator is mounted higher than the sink. The MAX manual rules it out.

Can I use PEX for the water supply?

Not with ThermaSol, whose manual rules out PEX and PVC tubing. Mr. Steam calls for brass piping or rigid copper tubing but allows a flexible copper, braided hose, PVC or PEX feed line where local codes permit.

Where does the steam head rough-in fitting go?

In new construction, set it before the wall is finished. ThermaSol's rule is 24 inches from the floor or tub rim and at least 6 inches from any corner (12 inches above the shower floor for the No-Touch); Mr. Steam's is 6 to 12 inches above the floor, or 6 inches above a tub's top edge, and not within 12 inches of a wall.

Is a drain pan required under the generator?

For ThermaSol, yes: a stainless steel drain pan is listed as included, and the manual says it must be installed, with its 3/4 inch drain plumbed to an approved drain. Mr. Steam strongly recommends a drip pan, which it sells separately.